5.9 Maximum frequency
 : Maximum frequency
Output frequency [Hz]
In case of

=80Hz
In case of

=60Hz
80Hz
60Hz
0 100% Frequency setting signal [%]
• This function determines the
maximum value in line with the
ratings of the motor and load.
• Maximum frequency cannot be
adjusted during operation. To
adjust, first stop the inverter.
If  is increased, adjust the upper limit frequency  as necessary.
[Parameter setting]
Title Function Adjustment range Default setting
 Maximum frequency ~ Hz 
Note: The output frequency is limited to a frequency 10.5 times as high as the base frequency (). Even if the
maximum frequency () or the upper limit frequency () is set above this frequency, this limitation is
imposed on the output frequency.
5.10 Upper limit and lower limit frequencies
 : Upper limit frequency
 : Lower limit frequency
Lower limit
frequency
0 100%
Output frequency [Hz]


Upper limit
frequency
0 100%
Output frequency [Hz]


Frequency
setting signal
Frequency
setting signal
+
Frequencies that go higher
than

will not be output.
+
The output frequency cannot
be set at less than

.
[Parameter setting]
Title Function Adjustment range Default setting
 Upper limit frequency ~ Hz  Refer to page K-2.
 Lower limit frequency ~ Hz 
• Function
1) Programs the range of frequencies output by the inverter (maximum output values).
2) This frequency is used as the reference for acceleration/deceleration time.
• Function
Programs the lower limit frequency that determines the lower limit of the output frequency and the upper limit
frequency that determines the upper limit of that frequency.