E6581528
H-5
8
8.2.2 Display of detailed information on a past trip
Details on a past trip (of trips 1 to 4) can be displayed, as shown in the table below, by pressing the key when the
trip record is selected in the status monitor mode.
Unlike the " Monitor display at tripping " in 8.4.2, details on a past trip can be displayed, even after the inverter is turned
off or reset.
Item displayed
Key
operated
LED display Description
Past trip 1
⇔ Past trip 1 (displayed alternately.)
Continuous trips
The number of time the same trip occurred in succession is displayed.
(, , , Unit: times)
Output frequency The operation frequency when the trip occurred is displayed.
Status monitor mode
(Rotating direction)
The direction of rotation is displayed. (:Forward run, :Reverse run)
Frequency command
value
The operation frequency command value is displayed.
(When =, Frequency command)
Output current
The inverter output current (load current) is displayed.
(When =, Output current)
Input voltage (DC
detection)
The inverter DC voltage is displayed. (Default setting unit: %)
(When =, Input voltage) [Note 3]
Output voltage
The inverter output voltage is displayed. (Default setting unit: %)
(When =, output voltage)
Input terminal
information
The ON/OFF status of each of the control signal input terminals (F, R,
RES, S1, S2, S3, RR/S4) is displayed in bits.
Output terminal
information
The ON/OFF status of each of the control signal output terminals
(OUT1, OUT2, FL) is displayed in bits.
Cumulative operation
time
The cumulative operation time when the trip occurred is displayed.
(0.01=1 hour, 1.00=100 hours)
Past trip 1
⇔ Press this key to return to past trip 1.
Note 1: Press the or key to change items displayed in the status monitor mode.
Note 2: You can switch between % and A (ampere)/V (volt), using the parameter (current/voltage unit
selection).
Note 3: The input voltage displayed is 1/
2
times as large as the rectified DC input voltage.
Note 4: The number of bars displayed varies depending on the setting of (logic output/pulse train output
selection). The bar representing the OUT1 terminal is displayed only when logic output function is assigned to it.
If = :The bar representing OUT1 is displayed.
If = :The bar representing OUT1 is not displayed.
Note 5: If there is no trip record, is displayed.
Note 6: The cumulative operation time increments only when the machine is in operation.
ENT
ENT
[Note 5]
[Note 1]
MODE
[Note 6]
[Note 4]
[Note 2]
[Note 2]
[Note 3]
[Note 2]