1. Basic parameter [2/4] Sensorless vector/vector with sensor (●:Effective, -:Ineffective)
Default setting
Vector control
Title
Communi
cation
No.
Function Adjustment range
Minimum
setting unit
(Panel/Communi
cation)
=
500V
-50Hz
=
575V
-60Hz
=
690V
-50Hz
Write
during
running
Speed
control
Torque
control
V/f
Constant
Reference
0015 V/f control mode selection
0:Constant torque characteristics
1:Voltage decrease curve
2:Automatic torque boost
3:Sensorless vector control 1 (speed)
4:Sensorless vector control 2 (speed/torque)
5:V/f 5-point setting
6:-(unsupported)
7:PG feedback control
8:PG feedback vector control
1/1 0 0 0 Disabled
-/-
-/-
●/-
●/-
●/-
-/-
-/-
-/●
-/●
-/-
-/-
-/-
-/-
●/-
-/-
-/-
-/-
-/●
●
●
-
-
-
●
-
-
-
5. 6
0016 Manual torque boost 1 0.0~30.0% 0.1/0.1 *1 *1 *1 Enabled - - ● 5. 7
0014 Base frequency 1 25.0~500.0Hz 0.1/0.01 50.0 60.0 50.0 Disabled ●/● ●/● ● 5. 8
0409 Base frequency voltage 1 50~990V 1/0.1 500 575 690 Disabled ●/● ●/● ● 5. 8
0011 Maximum frequency 30.0~500.0Hz 0.1/0.01 80.0 80.0 80.0 Disabled ●/● ●/● ● 5. 9
0012 Upper limit frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● 5. 10
0013 Lower limit frequency 0.0~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 10
0009 Acceleration time 1 0.1~6000 sec. 0.1/0.1 *2 *1 *1 *1 Enabled ●/● - ● 5. 2
0010 Deceleration time 1 0.1~6000 sec. 0.1/0.1 *2 *1 *1 *1 Enabled ●/● - ● 5. 2
0213 RR/S4 input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● 5. 11
0204 VI/II input point 2 frequency 0.0~ Hz 0.1/0.01 50.0 60.0 50.0 Enabled ●/● - ● 5. 11
0018
Preset speed operation
frequency 1
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0019
Preset speed operation
frequency 2
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0020
Preset speed operation
frequency 3
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0021
Preset speed operation
frequency 4
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0022
Preset speed operation
frequency 5
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0023
Preset speed operation
frequency 6
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0024
Preset speed operation
frequency 7
~ Hz 0.1/0.01 0.0 0.0 0.0 Enabled ●/● - ● 5. 12
0008
Forward run/reverse run
selection (operation panel
operation)
0:Forward run
1:Reverse run
2:Forward run (Forward/reverse switchable on
operation panel)
3:Reverse run (Forward/reverse switchable on
operation panel)
1/1 0 0 0 Enabled ●/● ●/● ● 5. 13
*1: Default values vary depending on the capacity. ⇒ See the table of K-46.
*2: Changing the parameter enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).