Note -
Reconnect the cables of the external interface in their original positions by referring to
the notes that you made prior to the start of maintenance.
Note -
See the procedure for system-stopped maintenance for inactive/cold maintenance in a
single-chassis configuration.
Note -
Use the DR of the system board on a physical partition for active/cold maintenance.
For the XCP and Oracle VM Server for SPARC/SRU versions that correspond to the DR, see
the latest Product Notes.
Note -
Active/cold maintenance can be performed only for a building block configuration.
Note -
In the case of a dual power feed, connect the power cords in their original positions by
referring to the record that you made before the start of maintenance.
■
Crossbar cable
■
XSCF BB control cable
■
XSCF DUAL control cable
■
LAN cable
12.
Lift the cable support to fix i t.
For details, see "6.5.2 Fixing the cable support."
14.6 Restoring the System
This section describes the procedure for restoring the system after installing the PSU
backplane unit. The restoration procedure differs depending on the maintenance
type as follows:
■
Active/Cold maintenance
■
Inactive/Cold maintenance
■
System-stopped maintenance
14.6.1 Active/Cold maintenance
1.
Connect all the pow er c ords to t he PSU backplane unit o f the chassis
requiring mai nten ance.
For details, see "6.5.1 Installing the power cord."
2.
Return t o the op eration of the XSCF firm w are replacefru command to confirm
that th e chassis has been incorporat ed into the system.
Fujitsu M10-4/Fujitsu M10-4S/SPARC M10-4/SPARC M10-4S Service Manual
・
December 2013276