Lucent Technologies R8r Server User Manual


 
DEFINITY Enterprise Communications Server Release 8.2
Upgrades and Additions for R8r
555-233-115
Issue 1
April 2000
Adding or Removing Cabinet Hardware
6-121Add a Switch Node Carrier (High or Critical Reliability)
6
Reseat DEFINITY LAN Gateway System
1. Reseat the LAN Gateway assembly into its backplane connectors.
Reseat DEFINITY AUDIX System
1. Reseat the AUDIX assembly to its backplane connectors.
Power Up System
1. At each EPN, if present, set the main circuit breaker to ON.
2. At the PPN, set the main circuit breaker to ON.
3. The system performs the level 4 rebooting process, loading the system
program and default or current translations from the disk. Rebooting takes
5 to 11 minutes.
NOTE:
Ignore alarms for now.
4. Type
reset system 4
and press
Enter to copy the translations from
removable media to memory.
5. Clear any alarms.
6. Type
save translation [both]
and press
Enter if translation changes were
made in Step 8 above.
7. Type
restore disk [both] full
and press
Enter to copy the translations from
removable media to disk.
8. After the system reboot is finished and all trouble cleared, verify that the
EMERGENCY TRANSFER CONTROL switch is set to AUTO. This restores
the system to the normal operating mode.
Restart DEFINITY LAN Gateway System
1. Log onto the DEFINITY LAN Gateway.
2. When the main menu appears, select
Maintenance
.
3. Select
Reset System
from the
Maintenance
menu.
4. Select
Restart System
from the
Reset System
menu.