Omron CQM1H-SCB41 Computer Hardware User Manual


 
9-2SectionBoard Replacement
128
Error
code
RemedyCauseError detailsIndicator
2 Hex No display Sequence
number error
The
communications
sequence number
specified in bits 00
to 11 of the
PMCR(––)
instructions C
operand is not
registered.
Correct the communications sequence
number.
Use CX-Protocol to register the
specified communications sequence
number.
3 Hex ERR/ALM
: Flashing
Receive data
write range
overflow error
The data range of
the specified area
is exceeded when
data is being
written to or read
from the I/O
memory of the
CPU Unit.
For operand specification:
Check the PMCR(––) instruction S and
D operand specifications.
For direct specification of link words:
Use CX-Protocol to check the specified
range.
4 Hex ERR/
ALM:
Flashing
Protocol data
syntax error
There is a code
that cannot be
executed during
protocol execution.
Check the following items and correct
the problem.
Check whether the total specified
number of link words in the area (O1,
O2, I1, I2) exceeds 128.
The same area with link word
specification is used by both ports 1
and 2.
A write instruction with constant
specification is specified.
An EM Area read/write instruction is
specified as an interrupt notification.
There are more than 30 write
attributes set for one message.
The length of a send/receive message
is set to 0 bytes.
The length of a send/receive message
is longer than 127 bytes.
No messages are registered for matrix
reception.
Both RTS/CTS flow control and
Xon/Xoff flow control are set for the
same transmission line.
5 Hex ERR/
ALM:
Flashing
Protocol macro
execution error
during port
initialization
The PMCR
instruction was
executed while the
port was being
initialized.
Check if the PMCR instruction was
executed during any one of the following
processes.
While the serial communications port
was being restarted.
While the serial communications mode
in the PC system setup of the Serial
Communications Board was being
modified using the STUP instruction.
While the serial communications mode
in the PC system setup of the Serial
Communications Board was being
modified using the Programming
Device.