Appendix G
E5jJ Temperature Controller Protocol
239
Read Output Value (Sequence No. 211)
Reads the output value and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Output value
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 Output value
(4 digits BCD)
0000 to 9999
When the left digit is –1, A is set and when
it is –, F is set.
Read Process Value (Sequence No. 212)
Reads the process value and status data and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
Process value
Status data
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0003
+1 Process value (4 digits BCD) 0000 to 9999
When the left digit is –1, A is set and when
it is –, F is set.
+2 Status data (4 digits Hex) 0000 to 9999
Read Set Point Limit (Sequence No. 213)
Reads the set point limits and stores the results in the specified word.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.