Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
199
Read Hysteresis (Sequence No. 109)
Reads the hysteresis and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Hysteresis
~ ~
Cooling hysteresis
Hysteresis
Cooling hysteresis
Channel 0
Channel 7
Hysteresis
Cooling hysteresis
Channel 1
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Hysteresis (4 digits BCD)
0000 to 0999
+2 Channel 0
Cooling hysteresis (4 digits BCD)
0000 to 0999
D
D
D
+15 Channel 7
Hysteresis (4 digits BCD)
0000 to 0999
+16 Channel 7
Cooling hysteresis (4 digits BCD)
0000 to 0999
Read Operation Status (Sequence No. 110)
Reads the operation status of the E5ZE and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+8
Status code
~ ~
Status code
Status code
Channel 0
Channel 7
Channel 1