Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix C
E5jK Digital Controller Read Protocol
158
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Cooling coefficient
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 Cooling coefficient (4 digits BCD) 0001 to 9999
Read Dead Band (Sequence No. 007)
Reads the dead band and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Dead band
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 Dead band (4 digits BCD) A999 to 9999
F indicates a negative value and A
indicates 1.
Read Manual Reset Value (Sequence No. 008)
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Manual reset value
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 Manual reset value (4 digits BCD) 0000 to 1000