Appendix EE5ZE Temperature Controller Read Protocol
192
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+15
+16
Set point (rightmost 4 digits)
~ ~
Set point (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Channel 0
Channel 7
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+2 Channel 0
Set point (leftmost 1 digit)
(1 digit BCD)
F indicates a negative value.
D
D
D
+15 Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer the manual for the E5ZE.
+16 Channel 7
Set point (leftmost 1 digit)
(1 digit BCD)
F indicates a negative value.
Read Process Value (Sequence No. 101)
Reads the process values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Process value (rightmost 4 digits)
~ ~
Process value (leftmost 1 digit)
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Channel 0
Channel 7
Process value (rightmost 4 digits)
Process value (leftmost 1 digit)
Channel 1