Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
219
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0010 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Input shift value (4 digits BCD)
0000 to 0999
+3 Channel 1
Input shift value (4 digits BCD)
0000 to 0999
+4 Channel 2
Input shift value (4 digits BCD)
0000 to 0999
D
D
D
+8 Channel 6
Input shift value (4 digits BCD)
0000 to 0999
+9 Channel 7
Input shift value (4 digits BCD)
0000 to 0999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Manual Reset Value (Sequence No. 163)
Writes the manual reset values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
(Undefined)
Unit No.
Manual reset value
Manual reset value
Channel 0
Channel 1
Manual reset value
Channel 2
Manual reset value
Channel 3
Manual reset value
Channel 4
Manual reset value
Channel 5
Manual reset value
Channel 6
Manual reset value
Channel 7
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0010 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Manual reset value
(4 digits BCD)
0000 to 1000
+3 Channel 1
Manual reset value
(4 digits BCD)
0000 to 1000
+4 Channel 2
Manual reset value
(4 digits BCD)
0000 to 1000
D
D
D
+8 Channel 6
Manual reset value
(4 digits BCD)
0000 to 1000
+9 Channel 7
Manual reset value
(4 digits BCD)
0000 to 1000
Receive Data Word Allocation (3rd Operand of PMCR)
None.