Appendix EE5ZE Temperature Controller Read Protocol
193
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+2 Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
F indicates a negative value.
D
D
D
+15 Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+16 Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
F indicates a negative value.
Read Output Values (Sequence No. 102)
Reads the output values of the control outputs and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Output value
~ ~
Cooling output value
Output value
Channel 0
Channel 7
Channel 1
Cooling output value
Output value
Cooling output value