Appendix C
E5jK Digital Controller Read Protocol
160
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
SP ramp time unit
SP ramp set value
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0003
+1 SP ramp time unit (4 digits BCD) 0000: s, 0001: hr
+2 SP ramp set value (4 digits BCD) 0000 to 9999
Read LBA Detection Time (Sequence No. 012)
Reads the LBA (loop break alarm) detection time and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
LBA detection time
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 LBA detection time (4 digits BCD) 0000 to 9999