Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix D
E5jK Digital Controller Write Protocol
178
Write Level 1 Parameters 1 (Sequence No. 066)
Writes parameters in level 1 (alarm value 1, alarm value 2, alarm value 3, proportional band, integral time, and
derivative time) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+51
+52
+53
+54
+55
+56
+57
Alarm value 1
Alarm value 2
Alarm value 3
~ ~
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
1st unit
8th unit (max.)
Proportional band
Integral time
Integral time
Derivative time
Derivative time
Number of send data words
(Undefined) Unit No.
Number of units
(Undefined) Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
Number of units 7 + 2
+1 Number of units (4 digits BCD) 0001 to 0008
+2 1st unit
Unit No. (2 digits BCD)
00 to 31
+3 1st unit
Alarm value 1 (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.
+4 1st unit
Alarm value 2 (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.
+5 1st unit
Alarm value 3 (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.
+6 1st unit
Proportional band (4 digits BCD)
0001 to 9999
+7 1st unit
Integral time (4 digits BCD)
0000 to 3999
+8 1st unit
Derivative time (4 digits BCD)
0000 to 3999
D
D
D
+57
(max.)
8th unit
Derivative time (4 digits BCD)
0000 to 3999
Receive Data Word Allocation (3rd Operand of PMCR)
None.