Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix G
E5jJ Temperature Controller Protocol
233
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Save Set Point (Sequence No. 204)
Saves the set point.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Parameters 1 (Sequence No. 205)
Writes the set point, alarm value 1, alarm value 2, and a heater burnout alarm value to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+6
+122
+123
+124
+125
+126
(Undefined)
Unit No.
set point
~ ~
Alarm value 1
set point
Alarm value 1
1st unit
25th unit (max.)
Alarm value 2
Heater burnout alarm value
Alarm value 2
Heater burnout alarm value
Number of units
(Undefined)
Unit No.