Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
202
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Channel 0
Manual reset value
(4 digits BCD)
0000 to 1000
+2 Channel 1
Manual reset value
(4 digits BCD)
0000 to 1000
D
D
D
+8 Channel 7
Manual reset value
(4 digits BCD)
0000 to 1000
Read Ramp Value (Sequence No. 115)
Reads the ramp values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Ramp value
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
(Undefined)
~ ~
Channel 0
Channel 7
Channel 1
Ramp value
Time unit (Undefined)
(Undefined) Ramp value
Time unit (Undefined)
(Undefined)
Time unit (Undefined)
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Ramp value (3 digits BCD)
000 to 999
+2 Channel 0
Time unit (one ASCII character)
S: Seconds; M: Minutes; H: Hours
D
D
D
+15 Channel 7
Ramp value (3 digits BCD)
000 to 999
+16 Channel 7
Time unit (one ASCII character)
S: Seconds; M: Minutes; H: Hours