Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
215
Write Alarm Temperature (Setting Unit 1) (Sequence No. 156)
Writes the alarm temperatures using a setting unit of 1 (4 digits)
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+30
+31
+32
+33
(Undefined)
Unit No.
Alarm 1 set value
~ ~
(Undefined)
Alarm 1 set value
(Undefined)
Channel 0
Channel 7
Alarm 2 set value
(Undefined)
Alarm 2 set value
(Undefined)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0034 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Alarm 1 set value
(4 digits BCD)
0000 to 9999
+3 Not used
+4 Channel 0
Alarm 2 set value
(4 digits BCD)
0000 to 9999
+5 Not used
D
D
D
+32 Channel 7
Alarm 2 set value
(4 digits BCD)
0000 to 9999
+33 Not used
Receive Data Word Allocation (3rd Operand of PMCR)
None.