Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
210
Connections
The connections are the same as that for the E5ZE Temperature Controller Read Protocol.
Write Set Point (Setting Unit 1) (Sequence No. 150)
Writes the set points using a setting unit of 1 (4 digits).
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Set point
~ ~
(Undefined)
Set point
(Undefined)
Channel 0
Channel 7
Set point
(Undefined)
Channel 1
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0018 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Set point
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
D
D
D
+16 Channel 7
Set point
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+17 Not used ---
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Note When the setting unit for the set point is 0.1 (5 digits), use Write Set Point (Setting Unit 0.1), Sequence