Appendix FE5ZE Temperature Controller Write Protocol
213
Write Control Period (Sequence No. 153)
Writes the control periods and cooling control periods.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Control period
~ ~
Cooling control period
Control period
Cooling control period
Channel 0
Channel 7
Control period
Cooling control period
Channel 1
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0018 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Control period (4 digits BCD)
0001 to 0099
+3 Channel 0
Cooling control period
(4 digits BCD)
0001 to 0099
+4 Channel 1
Control period (4 digits BCD)
0001 to 0099
+5 Channel 1
Cooling control period
(4 digits BCD)
0001 to 0099
D
D
D
+16 Channel 7
Control period (4 digits BCD)
0001 to 0099
+17 Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099
Receive Data Word Allocation (3rd Operand of PMCR)
None.