Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix G
E5jJ Temperature Controller Protocol
234
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
Number of units 5 + 2
+1 Number of units (4 digits BCD) 0001 to 0025
+2 1st unit
Unit No. (2 digits BCD)
00 to 31
+3 1st unit
set point (4 digits BCD)
0000 to 9999
+4 1st unit
Alarm value 1 (4 digits BCD)
0000 to 9999
+5 1st unit
Alarm value 2 (4 digits BCD)
0000 to 9999
+6 1st unit
Heater burnout alarm value 2
(4 digits BCD)
0000 to 9999
+7 2nd unit
Unit No. (2 digits BCD)
00 to 31
D
D
D
+126
(max.)
25th unit
Heater burnout alarm value 2
(4 digits BCD)
0000 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Parameters 2 (Sequence No. 206)
Writes the proportional bands, integral times, and derivative times to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+122
+123
+124
+125
(Undefined)
Unit No.
Proportional band
~ ~
Integral time
Proportional band
Integral time
1st unit
31th unit (max.)
Derivative time
Derivative time
Number of units
(Undefined)
Unit No.