Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
214
Write Output Mode (Sequence No. 154)
Writes the output mode (normal/reverse).
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
(Undefined)
Write code
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Write code (2 digits Hex) 00 to FF
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Alarm Mode (Sequence No. 155)
Writes the alarm modes for alarm 1 and alarm 2.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Alarm 1 set code
(Undefined)
~ ~
Channel 0
Channel 7
Channel 1
Alarm 1 set code
(Undefined) Alarm 2 set code
(Undefined) Alarm 1 set code
(Undefined) Alarm 2 set code
(Undefined)
(Undefined) alarm 2 set code
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0018 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Alarm 1 set code (2 digits Hex)
00 to 0C
+3 Channel 0
Alarm 2 set code (2 digits Hex)
00 to 0C
+4 Channel 1
Alarm 1 set code (2 digits Hex)
00 to 0C
+5 Channel 1
Alarm 2 set code (2 digits Hex)
00 to 0C
D
D
D
+16 Channel 7
Alarm 1 set code (2 digits Hex)
00 to 0C
+17 Channel 7
Alarm 2 set code (2 digits Hex)
00 to 0C
Receive Data Word Allocation (3rd Operand of PMCR)
None.