Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
194
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Output value (4 digits BCD)
0000 to 1000
+2 Channel 0
Cooling output value (4 digits BCD)
0000 to 1000
+3 Channel 1
Output value (4 digits BCD)
0000 to 1000
+4 Channel 1
Cooling output value (4 digits BCD)
0000 to 1000
D
D
D
+15 Channel 7
Output value (4 digits BCD)
0000 to 1000
+16 Channel 7
Cooling output value (4 digits BCD)
0000 to 1000
Read Set Point, Process Value, and Output Value
(Sequence No. 103)
Reads the set points, process values, and output values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to OF
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+5
+36
+37
+38
+39
+40
Set point (rightmost 4 digits)
~ ~
Set point (leftmost 1 digit)
Channel 0
Channel 7
Process value (rightmost 4 digits)
Output value
Process value (leftmost 1 digit)
Set point (rightmost 4 digits)
Set point (leftmost 1 digit)
Process value (rightmost 4 digits)
Output value
Process value (leftmost 1 digit)