Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
226
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0010 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Channel 0
Cooling coefficient (4 digits BCD)
0000 to 0100
+3 Channel 1
Cooling coefficient (4 digits BCD)
0000 to 0100
+4 Channel 2
Cooling coefficient (4 digits BCD)
0000 to 0100
D
D
D
+8 Channel 6
Cooling coefficient (4 digits BCD)
0000 to 0100
+9 Channel 7
Cooling coefficient (4 digits BCD)
0000 to 0100
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Start Control (Sequence No. 174)
Starts temperature control for all channels in the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Stop Operation or Control (Sequence No. 175)
Stops temperature control or manual operation for all channels of the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of send
data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
None.