Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
206
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Heater burnout detection current
~ ~
SSR failure detection current
Heater burnout detection current
SSR failure detection current
Channel 0
Channel 7
Heater burnout detection current
SSR failure detection current
Channel 1
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Heater burnout detection current
(4 digits BCD)
0000 to 0500
+2 Channel 0
SSR failure detection current
(4 digits BCD)
0000 to 0500
D
D
D
+15 Channel 7
Heater burnout detection current
(4 digits BCD)
0000 to 0500
+16 Channel 7
SSR failure detection current
(4 digits BCD)
0000 to 0500
Read Heater Current and SSR Leakage Current
(Sequence No.121)
Reads the heater currents and SSR leakage currents and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Heater current
~ ~
SSR leakage current
Heater current
SSR leakage current
Channel 0
Channel 7
Heater current
SSR leakage current
Channel 1