Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix G
E5jJ Temperature Controller Protocol
237
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
Number of units 4 + 1
+1 1st unit
Set point (4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
+2 1st unit
Alarm value 1 (4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
+3 1st unit
Alarm value 2 (4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
+4 1st unit
Heater burnout alarm value
(4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
+5 2nd unit
Set point (4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
D
D
D
+100
(max.)
25th unit
Heater burnout alarm value
(4 digits BCD)
0000 to 9999
When the left digit is 1, A is set and when
it is , F is set.
Read Parameters 2 (Sequence No. 209)
Reads the proportional bands, integral times, and derivative times for multiple units and stores the results in the
specified words.
Send Data Word Allocation (2nd Operand of PMCR)
(Undefined)
Unit No.
First word of
send data
Number of send data words+0
+1
+2
+32
(Undefined)
Unit No.
Number of units
~ ~
(max.)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
Number of units+ 2
+1 Number of units (4 digits BCD) 0001 to 0031
+2 1st unit
Unit No. (2 digits BCD)
00 to 31
+3 2nd unit
Unit No. (2 digits BCD)
00 to 31
D
D
D
+32
(max.)
31th unit
Unit No. (2 digits BCD)
00 to 31