Appendix I
K3Tj Intelligent Signal Processor Protocol
296
Read Set Value HH with Bank (Continuous Units)
(Sequence No. 323)
This sequence reads set value HH of a bank not in use for continuous units.
Send Data Word Allocation (2nd Operand of PMCR)
Bank No.
(Undefined)
Number of units
+0
+1
+2
+33
Number of send data wordsFirst word of
send data
~ ~
Bank No.(Undefined)
(Undefined)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 to 0034
+1 Number of units (2 digits BCD) 01 to 32
+2 Bank No. (2 digits BCD) 01 to 04
D
D
D
+ 33 Bank No. (2 digits BCD) Same as above
Receive Data Word Allocation (3rd Operand of PMCR)
The word allocation is similar to sequence No. 322 (Read Set Value with Bank (by Unit Number)).
Read Set Value H with Bank (Continuous Units)
(Sequence No. 324)
This sequence reads set value H of a bank not in use for continuous units. The word allocation is identical to that of
sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value L with Bank (Continuous Units)
(Sequence No. 325)
This sequence reads set value L of a bank not in use for continuous units. The word allocation is identical to that of
sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value LL with Bank (Continuous Units)
(Sequence No. 326)
This sequence reads set value LL of a bank not in use for continuous units. The word allocation is identical to that of
sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O5 with Bank (Continuous Units)
(Sequence No. 327)
This sequence reads set value O5 of a bank not in use for continuous units. The word allocation is identical to that
of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).
Read Set Value O4 with Bank (Continuous Units)
(Sequence No. 328)
This sequence reads set value O4 of a bank not in use for continuous units. The word allocation is identical to that
of sequence No. 323 (Read Set Value HH with Bank (Continuous Units)).