Appendix I
K3Tj Intelligent Signal Processor Protocol
293
Write Set Value O2 with Bank (Continuous Units)
(Sequence No. 315)
This sequence writes set value O2 of a bank not in use for continuous units. The word allocation is identical to that
of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Write Set Value O1 with Bank (Continuous Units)
(Sequence No. 316)
This sequence writes set value O1 of a bank not in use for continuous units. The word allocation is identical to that
of sequence No. 308 (Write Set Value HH with Bank (Continuous Units)).
Read Set Value (by Unit Number) (Sequence No. 317)
Reads set value HH, H, L, or LL.
Send Data Word Allocation (2nd Operand of PMCR)
Relevant unit No.(Undefined)
(Undefined)
Number of units
+0
+1
+2
+3
+64
+65
Number of send data wordsFirst word of
send data
~ ~
Relevant unit No.(Undefined)
Operand
Operand
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 to 0066
+1 Number of units
(2 digits BCD)
01 to 32
+2 Relevant unit No.
(2 digits BCD)
00 to 99
+3 Operand
(ASCII 2 characters)
4848 (“HH”), 4C4C (“LL”) 4F31 (“01”)
4820 (“H”), 4C20 (“L”) 4F35 (“05”)
D
D
D
+64 to
+65
Operand
(ASCII 2 characters)
Same as above
Receive Data Word Allocation (3rd Operand of PMCR))
End code
+0
+1
+2
+3
+94
+95
+96
Number of receive data wordsReceive data
storage words
~
~
Set value
(Undefined)
Set value
Set value
(Undefined)
Set value
End code(Undefined)
(Undefined)