Appendix EE5ZE Temperature Controller Read Protocol
205
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Channel 0
Output value change rate limit
(4 digits BCD)
0000 to 1000
+2 Channel 1
Output value change rate limit
(4 digits BCD)
0000 to 1000
D
D
D
+8 Channel 7
Output value change rate limit
(4 digits BCD)
0000 to 1000
Read HB Alarm and HS Alarm Valid Channels
(Sequence No. 119)
Reads the valid or invalid channels for HB alarms and HS alarms and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
(Undefined) Set code
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Set code (2 digits Hex) 00 to FF
Read Heater Burnout and SSR Failure Detection Currents
(Sequence No. 120)
Reads the heater burnout and SSR failure detection currents and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F