Appendix EE5ZE Temperature Controller Read Protocol
208
Read Cooling Coefficient (Sequence No. 123)
Reads the cooling coefficients and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+8
Cooling coefficient
~ ~
Cooling coefficient
Cooling coefficient
Channel 0
Channel 7
Channel 1
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Channel 0
Cooling coefficient (4 digits BCD)
0000 to 0100
+2 Channel 1
Cooling coefficient (4 digits BCD)
0000 to 0100
D
D
D
+8 Channel 7
Cooling coefficient (4 digits BCD)
0000 to 0100