Appendix EE5ZE Temperature Controller Read Protocol
200
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Channel 0
Status code (4 digits Hex)
0000 to FFFF
+2 Channel 1
Status code (4 digits Hex)
0000 to FFFF
D
D
D
+8 Channel 7
Status code (4 digits Hex)
0000 to FFFF
Read Error Status (Sequence No. 111)
Reads the contents of errors if they have occurred and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Status code
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Status code (4 digits BCD) 0000 to FFFF
Read Setting Unit (Sequence No. 112)
Reads the setting units and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
Set code
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0002
+1 Set code (4 digits BCD) 0000: unit of 1
0001: unit of 0.1