Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix D
E5jK Digital Controller Write Protocol
181
Write Level 2 Parameters 2 (Sequence No. 069)
Writes parameters in level 2 (input digital filter, alarm 1 hysteresis, alarm 2 hysteresis, alarm 3 hysteresis, input
shift upper limit, and input shift lower limit) to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
+0
+1
+2
+3
+4
+5
+6
+7
+8
+51
+52
+53
+54
+55
+56
+57
Input digital filter
alarm 1 hysteresis
alarm 2 hysteresis
~ ~
Input digital filter
alarm 1 hysteresis
alarm 2 hysteresis
alarm 3 hysteresis
1st unit
8th unit (max.)
alarm 3 hysteresis
Input shift upper limit
Input shift upper limit
Input shift lower limit
Input shift lower limit
Number of send data words
(Undefined) Unit No.
Number of units
(Undefined) Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
Number of units 7 + 2
+1 Number of units (4 digits BCD) 0001 to 0008
+2 1st unit
Unit No. (2 digits BCD)
00 to 31
+3 1st unit
Input digital filter (4 digits BCD)
0000 to 9999
+4 1st unit
Alarm 1 hysteresis
(4 digits BCD)
0001 to 9999
+5 1st unit
Alarm 2 hysteresis
(4 digits BCD)
0001 to 9999
+6 1st unit
Alarm 3 hysteresis
(4 digits BCD)
0001 to 0099
+7 1st unit
Input shift upper limit (4 digits BCD)
000 to 9999
+8 1st unit
Input shift lower limit (4 digits BCD)
000 to 9999
D
D
D
+57
(max.)
8th unit
Input shift lower limit (4 digits BCD)
000 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.