Appendix D
E5jK Digital Controller Write Protocol
177
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Level 0 Parameters (Sequence No. 065)
Writes parameters (set points) in level 0 to multiple units.
Send Data Word Allocation (2nd Operand of PMCR)
(Undefined)
Unit No.
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+16
+17
(Undefined)
Unit No.
Number of units
(Undefined)
Unit No.
~ ~
Set point
Set point
Set point
1st unit
2nd unit
8th unit (max.)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
Number of units 2 + 2
+1 Number of units (4 digits BCD) 0001 to 0008
+2 1st unit
Unit No. (2 digits BCD)
00 to 31
+3 1st unit
Set point (4 digits BCD)
Set point lower limit to upper limit
D
D
D
+17
(max.)
8th unit
Set point (4 digits BCD)
Set point lower limit to upper limit
Receive Data Word Allocation (3rd Operand of PMCR)
None.