Appendix D
E5jK Digital Controller Write Protocol
173
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Cooling Coefficient (Sequence No. 053)
Writes the cooling coefficient.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
Cooling coefficient
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Cooling coefficient (4 digits BCD) 0001 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Dead Band (Sequence No. 054)
Writes the dead band.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
Dead band
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Dead band (4 digits BCD) 0000 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Manual Reset Value (Sequence No. 055)
Writes the manual reset value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
Manual reset value
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Manual reset value (4 digits BCD) 0000 to 1000
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Hysteresis (Sequence No. 056)
Writes the hysteresis for heating and for cooling.