Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
204
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+29
+30
+31
+32
Output value lower limit
~ ~
Output value upper limit
Output value lower limit
Channel 0
Output value upper limit
Cooling control output value lower limit
Cooling control output value upper limit
Cooling control output value lower limit
Cooling control output value upper limit
Channel 7
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0033
+1 Channel 0
Output value lower limit
(4 digits BCD)
0000 to 1000
+2 Channel 0
Output value upper limit
(4 digits BCD)
0000 to 1000
+3 Channel 0
Cooling control output value upper
limit (4 digits BCD)
0000 to 1000
+4 Channel 0
Cooling control output value upper
limit (4 digits BCD)
0000 to 1000
D
D
D
+31 Channel 7
Cooling control output value upper
limit (4 digits BCD)
0000 to 1000
+32 Channel 7
Cooling control output value upper
limit (4 digits BCD)
0000 to 1000
Read Output Value Change Rate Limit (Sequence No. 118)
Reads the output value change rate limits and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+8
Output value change rate limit
~ ~
Output value change rate limit
Output value change rate limit
Channel 0
Channel 7
Channel 1