Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
196
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0025
+1 Channel 0
Constant P (4 digits BCD)
0000 to 9999
+2 Channel 0
Constant I (4 digits BCD)
0000 to 3999
+3 Channel 0
Constant D (4 digits BCD)
0000 to 3999
D
D
D
+22 Channel 7
Constant P (4 digits BCD)
0000 to 9999
+2 3 Channel 7
Constant I (4 digits BCD)
0000 to 3999
+24 Channel 7
Constant D (4 digits BCD)
0000 to 3999
Read Control Period (Sequence No. 105)
Reads the control periods and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+15
+16
Control period
~ ~
Cooling control period
Control period
Cooling control period
Channel 0
Channel 7
Control period
Cooling control period
Channel 1
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0017
+1 Channel 0
Control period (4 digits BCD)
0001 to 0099
+2 Channel 0
Cooling control period
(4 digits BCD)
0001 to 0099
D
D
D
+15 Channel 7
Control period (4 digits BCD)
0001 to 0099
+16 Channel 7
Cooling control period
(4 digits BCD)
0001 to 0099