Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix D
E5jK Digital Controller Write Protocol
176
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Digital Filter (Sequence No. 062)
Writes the input digital filter.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
Input digital filter
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Input digital filter (4 digits BCD) 0000 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Alarm Hysteresis (Sequence No. 063)
Writes the alarm 1 hysteresis and alarm 2 hysteresis.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
(Undefined)
Unit No.
Alarm 1 hysteresis
Alarm 2 hysteresis
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Alarm 1 hysteresis
(4 digits BCD)
0001 to 9999
+3 Alarm 2 hysteresis
(4 digits BCD)
0001 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Shift Value (Sequence No. 064)
Writes the input shift upper limit and input shift lower limit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
(Undefined)
Unit No.
Input shift upper limit
Input shift lower limit
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Input shift upper limit (4 digits BCD) 0000 to 9999
+3 Input shift lower limit (4 digits BCD) 0000 to 9999