Appendix EE5ZE Temperature Controller Read Protocol
201
Read Input Shift Value (Sequence No. 113)
Reads the input shift values and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+8
Input shift value
~ ~
Input shift value
Input shift value
Channel 0
Channel 7
Channel 1
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0009
+1 Channel 0
Input shift value (4 digits BCD)
0000 to 0999
F indicates a negative number.
+2 Channel 1
Input shift value (4 digits BCD)
0000 to 0999
F indicates a negative number.
D
D
D
+8 Channel 7
Input shift value (4 digits BCD)
0000 to 0999
F indicates a negative number.
Read Manual Reset Value (Sequence No. 114)
Reads the manual reset value and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+8
Manual reset value
~ ~
Manual reset value
Manual reset value
Channel 0
Channel 7
Channel 1