Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix C
E5jK Digital Controller Read Protocol
169
Receive Data Word Allocation (3rd Operand of PMCR)
Input digital filter
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+5
+6
+43
+44
+45
+46
+47
+48
Input digital filter
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
~ ~
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
1st unit
8th unit (max.)
Input shift lower limit
Input shift lower limit
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
Number of units 6 + 1
+1 1st unit
Input digital filter (4 digits BCD)
0000 to 9999
+2 1st unit
Alarm 1 hysteresis
(4 digits BCD)
0001 to 9999
+3 1st unit
Alarm 2 hysteresis
(4 digits BCD)
0001 to 9999
+4 1st unit
Alarm 3 hysteresis
(4 digits BCD)
0001 to 9999
+5 1st unit
Input shift upper limit (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.
+6 1st unit
Input shift lower limit (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.
D
D
D
+48
(max.)
8th unit
Input shift lower limit (4 digits BCD)
A999 to 9999
F indicates a negative value and A
indicates 1.