Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix EE5ZE Temperature Controller Read Protocol
195
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0041
+1 Channel 0
Set point (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+2 Channel 0
Set point (leftmost 1 digit)
(1 digit BCD)
+3 Channel 0
Process value (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+4 Channel 0
Process value (leftmost 1 digit)
(1 digit BCD)
+5 Channel 0
Output value (4 digits BCD)
0000 to 1000
D
D
D
+36 Channel 7
Set point (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+37 Channel 7
Set point (leftmost 1 digit)
(1 digit BCD)
+38 Channel 7
Process value (rightmost 4 digits)
(4 digits BCD)
Varies according to the temperature sensor
type. Refer to the manual for the E5ZE.
+39 Channel 7
Process value (leftmost 1 digit)
(1 digit BCD)
+40 Channel 0
Output value (4 digits BCD)
0000 to 1000
Read Proportional Band, Integral Time, and Derivative Time
(Sequence No. 104)
Reads the proportional bands (constant P), integral times (constant I), and derivative times (Constant D) and
stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+22
+23
+24
Constant P
~ ~
Constant I
Channel 0
Channel 7
Constant D
Constant P
Constant I
Constant D