Appendix FE5ZE Temperature Controller Write Protocol
227
Start Manual Operation (Sequence No. 176)
Starts manual operation based on the output values that were set for all channels of the specified Unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
None.