Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix FE5ZE Temperature Controller Write Protocol
218
Cancel Autotuning (Sequence No. 160)
Cancels Autotuning (AT) for all channels.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Setting Unit (Sequence No. 161)
Writes the setting unit.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
(Undefined)
Unit No.
Write code
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0003 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
+2 Write code (4 digits BCD) 0000: unit of 1
0001: unit of 0.1
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Input Shift Value (Sequence No. 162)
Writes the input shift values.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
+4
+5
+6
+7
+8
+9
(Undefined)
Unit No.
Input shift value
Input shift value
Channel 0
Channel 1
Input shift value
Channel 2
Input shift value
Channel 3
Input shift value
Channel 4
Input shift value
Channel 5
Input shift value
Channel 6
Input shift value
Channel 7