Appendix EE5ZE Temperature Controller Read Protocol
198
Read Alarm Temperatures (Sequence No. 108)
Reads the alarm temperatures and stores the results in the specified words.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
(Undefined)
Unit No.
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0002 (fixed)
+1 Unit No. (2 digits Hex) 00 to 0F
Receive Data Word Allocation (3rd Operand of PMCR)
Receive data
storage words
Number of receive data words+0
+1
+2
+3
+4
+29
+30
+31
+32
Alarm 1 set value (rightmost 4 digits)
~ ~
Alarm 1 set value (leftmost 1 digit)
Alarm 1 set value (rightmost 4 digits)
Alarm 1 set value (rightmost 1 digit)
Channel 0
Channel 7
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Alarm 2 set value (rightmost 4 digits)
Alarm 2 set value (leftmost 1 digit)
Offset Contents (data format) Data
+0 Number of receive data words
(4 digits BCD)
0033
+1 Channel 0
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
F indicates a negative number.
+2 Channel 0
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.
+3 Channel 0
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
F indicates a negative number.
+4 Channel 0
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.
D
D
D
+29 Channel 7
Alarm 1 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
F indicates a negative number.
+30 Channel 7
Alarm 1 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.
+31 Channel 7
Alarm 2 set value (rightmost 4 digits)
(4 digits BCD)
0000 to 9999
F indicates a negative number.
+32 Channel 07
Alarm 2 set value (leftmost 1 digit)
(4 digits BCD)
0000 to 0009
F indicates a negative number.