Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix K3Z4L Laser Micrometer Protocol
319
Sequence
No.
Ladder interfaceFunctionCommunications sequence
name
Sequence
No.
Receive
word
allocation
Send word
allocation
FunctionCommunications sequence
name
439 Data request (4000-series) Requests measurement data in the idle
measurement status or the latch data
generated by the measurement com-
mand.
No Yes
440 Forced positive zero
(4000-series)
Sets the forced zero direction to positive
(+).
No No
441 Forced negative zero
(4000-series)
Sets the forced zero direction to negative
().
No
No
442 Forced zero release (4000-se-
ries)
Releases the forced zero direction. No No
443 3Z4L initialize (4000-series) Clears the 3Z4L, sets the mm unit, and
clears the memory unit settings.
Yes No
444 General-purpose command 1 Used to send data of a specified data
length, and receive only OK as the re-
ceive data.
Yes No
445 General-purpose command 2 Used to send data of a specified data
length, and receive data other than OK.
Yes Yes
*1 Depends on the measurement contents.
Note Ladder Interface Settings
YES: User settings are required for the 2nd and 3rd operands of PMCR.
NO: Send word allocation: Set a dummy word address for the 3rd operand (D).
Receive word allocation: Set the constant 0000 for the 2rd operand (S).
Connections
The connections for the 3Z4L Laser Micrometer Protocol are shown below.
RS-232C Connection
Sensor
Signal cable
Controller
Serial Communica-
tions Board
RS-232C Port
FG
SD
RD
RS
CS
DR
ER
SG
1
2
3
4
5
7
8
9
Pin No.
Serial Communications Board:
D-sub 9 pin (female)
Controller: D-sub
25 pin (female)
Signal
name
FG
TXD
RXD
RTS
CTS
DSR
SG
DTR
1
2
3
4
5
6
7
20
Pin No.
Signal
name
CQM1H