Omron CQM1H-SCB41 Computer Hardware User Manual


 
Appendix D
E5jK Digital Controller Write Protocol
174
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
(Undefined)
Unit No.
Hysteresis (heating)
Hysteresis (cooling)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Hysteresis (heating)
(4 digits BCD)
0001 to 9999
+3 Hysteresis (cooling)
(4 digits BCD)
0001 to 9999
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write Control Period (Sequence No. 057)
Writes the control period for heating and for cooling.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
(Undefined)
Unit No.
Control period (heating)
Control period (cooling)
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 Control period (heating)
(4 digits BCD)
0001 to 0099
+3 Control period (cooling)
(4 digits BCD)
0001 to 0099
Receive Data Word Allocation (3rd Operand of PMCR)
None.
Write SP Ramp Time Unit and Set Value (Sequence No. 058)
Writes the SP ramp time unit and SP ramp set value.
Send Data Word Allocation (2nd Operand of PMCR)
First word of
send data
Number of send data words+0
+1
+2
+3
(Undefined)
Unit No.
SP ramp time unit
SP ramp set value
Offset Contents (data format) Data
+0 Number of send data words
(4 digits BCD)
0004 (fixed)
+1 Unit No. (2 digits BCD) 00 to 31
+2 SP ramp time unit (4 digits BCD) 0000: Minutes
0001: Hours
+3 SP ramp set value (4 digits BCD) 0000 to 9999