DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-342CUST-ALM (Customer-Provided Alarming Device)
10
Table 10-109. TEST #115 Customer-Provided Alarming Device Test
Error
Code
Test
Result Description/Recommendation
(blank)
1000
2029
ABORT Internal system error
1. Try the command at 1-minute intervals a maximum of 5 times.
PASS The switch software successfully sent the request to the
Maintenance/Tape Processor or EPN Maintenance circuit pack to turn on
the CPAD. The CPAD must be physically inspected to verify that it is
working. If the CPAD is working and the customer has complained that the
CPAD did not indicate a system alarm when it occurred, then check the
administered levels for turning on the CPAD via the Display
System-Parameter Maintenance screen form. Compare these levels with
the customer’s specifications. If Test #115 passes, and the CPAD is not
being activated, check the connection of the CPAD to the
Maintenance/Tape Processor or EPN Maintenance circuit pack. If the
CPAD can be activated but cannot be deactivated, first check to make
sure Emergency Transfer is not activated in the affected port network via
the status system command. Emergency Transfer can be forced to
manual OFF by the Emergency Transfer switch on the Maintenance/Tape
Processor or EPN Maintenance circuit pack. If Emergency Transfer is OFF
and the CPAD still cannot be deactivated, check the administered levels
for the CPAD via the Display System-Parameter Maintenance screen form
and compare against the alarm levels currently present in the system
(display alarms command).
Continued on next page