Page 10-1042PR-MAINT (Maintenance Processor [TN790 RISC Systems])
10
1018 ABORT The test has been disabled via administration.
1. To enable the test, issue the change system-parameters maintenance
command, and set the Test Remote Access Port field to ‘‘y.’’
2. Rerun the test.
1030 ABORT This test is not run on the Standby SPE.
1050 ABORT System could not determine if the testing of the INADS port is administered.
1. Enter change system-parameters maintenance command, and verify
the entry for the Test Remote Access Port field.
2. Retry at 1-minute intervals a maximum of 5 times.
1131 ABORT INADS port is busy because the system is reporting alarms to INADS, or
because INADS is dialed into the system.
1. If INADS is communicating with the switch the INADS trunk is working.
There is no need to run this test.
2. Or if required. Wait about ten minutes (until the INADS session is
terminated) and then re-enter the command.
1000 ABORT System software resources required to run this test are not available.
2033 Internal system error
1. Retry at 1-minute intervals a maximum of 5 times.
2000 ABORT MTP did not respond to the test request.
Repeat test at 1-minute intervals a maximum of 5 times.
If only the MTP Analog Loop Around Test is aborting, escalate the problem.
If all MTP tests are aborting, execute the test processor a/b long command
in order to reset MTP, and examine the results of the MTP Reset Test (#101).
2500 ABORT Internal system error
Repeat the command at 1-minute intervals a maximum of 5 times.