Maintenance Object Repair Procedures
Page 10-1141SHDW-LNK (Memory Shadowing Link)
10
2049
(cont’d.)
FAIL Refer to the "Replacing Defective SPE Circuit Packs" section in Chapter 6 to
understand how to correctly replace the Duplication-Interface circuit pack.
If none of the four red LEDs are lit AND if this is the fifth attempt to clear
the problem (the Standby SPE Processor, Standby SPE Memory, and
both Duplication Interface circuit packs have been replaced), escalate
the problem.
9. Issue the refresh spe-standby command to put the Standby SPE in
Standby Mode. This command may have to be issued multiple times. If the
refresh spe-standby command successfully completes five times without
the Standby SPE becoming labeled "standby" on the status system form,
wait 20 minutes. This does not include cases where the command
completes with the terminal message line errors "Refresh not successful;
use ‘display errors’ to check for STBY-SPE errors" or "Cannot interrupt
Standby SPE while entering maintenance mode; please try later." Issue the
refresh spe-standby command once more.
10. Repeat the test.
11. Issue the test spe-standby long command to thoroughly test all Standby
SPE components.
2050 FAIL The Standby SPE Maintenance/Tape Processor released the Standby SPE
Processor with a request to perform the RAM Checksum Test on Standby SPE
Memory. The RAM checksum was correct and the two special Standby SPE
Memory locations contain the same time stamp value as the one shadowed
over from the Active SPE; however, that time stamp value is significantly
different from the value of the Standby SPE’s Time-of-Day clock. This indicates
that either the Active SPE Time-of-Day clock has never been set (for example,
at system installation time) or that the Active SPE Time-of-Day clock was set
(with a significant change) while shadowing to the Standby SPE was disabled.
1. Issue the refresh spe-standby command to put the Standby SPE in
Standby Mode. This command may have to be issued multiple times. If the
refresh spe-standby command successfully completes five times without
the Standby SPE becoming labeled "standby" on the status system form,
wait 20 minutes. This does not include cases where the command
completes with the terminal message line errors "Refresh not successful;
use ‘display errors’ to check for STBY-SPE errors" or "Cannot interrupt
Standby SPE while entering maintenance mode; please try later." Issue the
refresh spe-standby command once more.
2. Issue the set time command and set the Time-of-Day clock.
3. Repeat the test.
Table 10-406. TEST #318 Shadow Link Test — Continued
Error
Code
Test
Result Description/ Recommendation
Continued on next page