DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-216CABINET (Cabinet Sensors)
10
10. Replace the fan assembly cover or panel.
Hardware Error Log Entries and Test to Clear
Values
System Technician-Demanded Tests:
Descriptions and Error Codes
Always investigate tests in the order presented in the table below when
inspecting errors in the system. By clearing error codes associated with the
Battery & Battery Charger Query Test
, for example, you may also clear errors
generated from other tests in the testing sequence.
1. Run the Short Test Sequence first. If all tests pass, run the Long Test Sequence. Refer to the
appropriate test description and follow the recommended procedures.
Cabinet Sensors Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Cabinet Temperature
Query Test (#122)
MINOR ON test environment P sh r 3
257 Any Cabinet Temperature
Query Test (#122)
MAJOR ON test environment P sh r 3
Table 10-75. System Technician-Demanded Tests: CABINET
Order of Investigation
Short Test
Sequence
Long Test
Sequence D/ND
1
Battery & Battery Charger Query Test (#5) (a) X X ND
AC Power Query Test (#78) (b) X X ND
Power Unit Query Test (carrier E) (#127) (c) X X ND
Power Unit Query Test (carrier D) (#127) (c) X X ND
Power Unit Query Test (carrier A) (#127) (c) X X ND
Power Unit Query Test (carrier B) (#127) (c) X X ND
Power Unit Query Test (carrier C) (#127) (c) X X ND
Emergency Transfer Query Test (#124) (d) X X ND
Cabinet Temperature Query Test (#122) X X ND
Continued on next page