DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-1031POWER (Battery & Battery Charger for DC-Powered Systems
10
POWER (Battery & Battery Charger
for DC-Powered Systems
NOTE:
For environment maintenance, the PPN or EPN cabinet configuration
aspects for a High or Critical Reliability system are irrelevant.
The environment maintenance strategy to be used depends on both the cabinet
configuration and the type of powering. Refer to the DC-POWER (DC Power)
Maintenance documentation for environment maintenance strategy.
In a DC-powered cabinet, the POWER MO still exists, but serves no functional
purpose. Because the system cannot determine the type of powering provided,
all POWER tests should always pass or abort. Since the tests should never fail,
POWER alarms should not be raised.
Error Log Entries and Test to Clear Values
1. Where P is an appropriate port network number determined via the Port field from the
Alarm or Error Log.
MO Name (in
Alarm Log)
Alarm
Level Initial Command to Run
1
Full Name of MO
POWER MINOR test environment P Battery & Battery Charger
Table 10-351. Power Error Log Entries
Error
Type
Aux
Data Associated Test
Alarm
Level
On/Off
Board Test to Clear Value
0
1
0 Any Any Any test environment P sh r 1
1 Any Battery & Battery Charger
Query Test (#5) (Error Code 8)
MINOR ON test environment P sh r 1
257 Any Battery & Battery Charger
Query Test (#5) (Error Code 4)
MINOR ON test environment P sh r 1
Continued on next page