DEFINITY Enterprise Communications Server Release 6
Maintenance for R6vs/si
555-230-127
Issue 1
August 1997
Maintenance Object Repair Procedures
Page 10-218CABINET (Cabinet Sensors)
10
Table 10-76. TEST #122 Cabinet Temperature Query Test
[Non-Variable Speed Fans]
Error
Code
Test
Result Description/ Recommendation
1000 ABORT System resources required to run this test are not available.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
2000 ABORT Response to the test request was not received within the allowable time
period.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to ABORT with Error Code 2000, check for system
powering problems with the A carrier (PPN or EPN). Look for and
resolve all AC-POWER and CARR-POW alarms in a multicarrier
cabinet system or DC-POWER alarms in a single-carrier cabinet
system. Then, repeat the test.
3. If the test continues to ABORT with a Error Code 2000, check for and
resolve all DUPINT (Duplication Interface) errors in a Duplicated
Option PPN, PR-MAINT (Maintenance/Tape Processor) errors in a
standard PPN, or MAINT (EPN Maintenance circuit pack) errors in an
EPN. Then, repeat the test.
4. If the test continues to ABORT with a Error Code 2000, escalate the
problem.
2029 ABORT Internal System Error.
1. Retry the command at one-minute intervals a maximum of five times.
2. If the test continues to abort, escalate the problem.
Continued on next page